ABB RELION 620 Series Technical Manual page 871

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
5.8.6
5.8.7
Table 828:
UPCALH Non group settings (Basic)
Parameter
Values (Range)
Operation
Operate pulse time
Signal pwr on delay
Table 829:
UPCALH Non group settings (Advanced)
Parameter
Values (Range)
CB open hold delay
5.8.8
620 series
Technical Manual
is used as a stand-alone function when an unknown circuit breaker open is detected,
the function output can be used as an information indication for the supervision
station.
Signals
Table 826:
UPCALH Input signals
Name
CB_OPEN_CMD
CB_POSCLOSE
CB_POSOPEN
SI_PWR_ON
Table 827:
UPCALH Output signals
Name
OPERATE
Settings
Unit
1=on
5=off
100...20000
ms
300...500
ms
Unit
300...500
ms
Technical data
Table 830:
UPCALH Technical data
Characteristic
Operate time accuracy
Type
Default
Description
BOOLEAN
0=False
CB open command, common
BOOLEAN
0=False
CB position closed
BOOLEAN
0=False
CB position open
BOOLEAN
0=False
Signal power on
Type
Description
BOOLEAN
Operate
Step
Default
1=on
1
100
1
300
Step
Default
1
300
Value
±1.0% of the set value or ±20 ms
Protection related functions
Description
Operation Off / On
Operate pulse time
Signal power on delay time
Description
CB open hold delay time
Section 5
865