ABB RELION 620 Series Technical Manual page 897

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
6.3.7
Table 847:
CTSRCTF Non group settings (Basic)
Parameter
Values (Range)
Operation
Min operate current
Max operate current
Max Ng Seq current
6.3.8
6.3.9
6.4
6.4.1
620 series
Technical Manual
Settings
Unit
1=on
5=off
0.01...0.50
xIn
1.00...5.00
xIn
0.01...1.00
xIn
Monitored data
Table 848:
CTSRCTF Monitored data
Name
INT_BLKD
CTSRCTF
Technical data
Table 849:
CTSRCTF Technical data
Characteristic
1)
Operate time
1) Including the delay of the output contact
Current transformer supervision for high-impedance
protection scheme HZCCxSPVC
Identification
Function description
Current transformer supervision for
high-impedance protection scheme for
phase A
Current transformer supervision for
high-impedance protection scheme for
phase B
Current transformer supervision for
high-impedance protection scheme for
phase C
Step
Default
1=on
0.01
0.02
0.01
1.30
0.01
0.10
Type
Values (Range)
BOOLEAN
0=False
1=True
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
<30 ms
IEC 61850
identification
HZCCASPVC
HZCCBSPVC
HZCCCSPVC
Section 6
Supervision functions
Description
Operation Off / On
Minimum operate current
Maximum operate current
Maximum I2 current in healthy set
Unit
Description
Function blocked
internally
Status
IEC 60617
ANSI/IEEE C37.2
identification
device number
MCS I_A
MCS I_A
MCS I_B
MCS I_B
MCS I_C
MCS I_C
891