Signals - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 3
Basic functions
L/R Control
Control FB input CTRL.LLN0.LocSta
TRUE
4)
CTRL_REM
CTRL_REM
FALSE
CTRL_ALL
FALSE
TRUE
4)
CTRL_ALL
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.17.10.8
182
L/R Control status
CTRL.LLN0.MltLev
1)
TRUE
TRUE
TRUE
TRUE

Signals

Table 187:
CONTROL input signals
Name
Type
CTRL_OFF
BOOLEAN
CTRL_LOC
BOOLEAN
CTRL_STA
BOOLEAN
CTRL_REM
BOOLEAN
CTRL_ALL
BOOLEAN
Table 188:
CONTROL output signals
Name
OFF
LOCAL
STATION
REMOTE
ALL
BEH_BLK
BEH_TST
L/R state
CTRL.LLN0.LocKeyHMI
3
7
6
5
Default
0
0
0
0
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1MRS757644 F
Control access
Local user
IEC 61850
client
2)
x
x
x
x
Description
Control input OFF
Control input Local
Control input Station
Control input Remote
Control input All
Description
Control output OFF
Control output Local
Control output Station
Control output Remote
Control output All
Logical device CTRL block
status
Logical device CTRL test status
Technical Manual
IEC 61850
client
3)
x
x
x
x
620 series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents