Name
Type
Flt loop
Enum
Flt distance
FLOAT32
Flt Dist quality
INT32
Flt loop resistance
FLOAT32
Flt loop reactance
FLOAT32
Flt phase reactance
FLOAT32
Flt point resistance
FLOAT32
Flt to Lod Cur ratio
FLOAT32
Equivalent load Dis
FLOAT32
XC0F Calc
FLOAT32
Pre fault time
Timestamp
A Pre Flt Phs A Magn
FLOAT32
A Pre Flt Phs A Angl
FLOAT32
A Pre Flt Phs B Magn
FLOAT32
A Pre Flt Phs B Angl
FLOAT32
A Pre Flt Phs C Magn
FLOAT32
A Pre Flt Phs C Angl
FLOAT32
V Pre Flt Phs A Magn
FLOAT32
V Pre Flt Phs A Angl
FLOAT32
V Pre Flt Phs B Magn
FLOAT32
V Pre Flt Phs B Angl
FLOAT32
V Pre Flt Phs C Magn
FLOAT32
V Pre Flt Phs C Angl
FLOAT32
A Flt Phs A Magn
FLOAT32
A Flt Phs A angle
FLOAT32
Table continues on next page
Protection related functions
Values (Range)
Unit
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-5=No fault
0.00...3000.00
pu
0...511
0.0...1000000.0
ohm
0.0...1000000.0
ohm
0.0...1000000.0
ohm
0.0...1000000.0
ohm
0.00...60000.00
0.00...1.00
0.0...1000000.0
ohm
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
Section 5
Description
Fault loop
Fault distance
Fault distance quality
Fault loop resistance
Fault loop reactance
Fault phase reactance
Fault resistance
Fault to load current ratio
Estimated equivalent
load distance
Estimated PhE
capacitive reactance of
the line
Pre-fault time
Pre-fault current phase A,
magnitude
Pre-fault current phase A,
angle
Pre-fault current phase B,
magnitude
Pre-fault current phase B,
angle
Pre-fault current phase
C, magnitude
Pre-fault current phase
C, angle
Pre-fault voltage phase
A, magnitude
Pre-fault voltage phase
A, angle
Pre-fault voltage phase
B, magnitude
Pre-fault voltage phase
B, angle
Pre-fault voltage phase
C, magnitude
Pre-fault voltage phase
C, angle
Fault current phase A,
magnitude
Fault current phase A,
angle