108
Service
10.1.3.2

PROFIsafe Address Set Using the Parameterization Tool

If the setting of the coding switch of the I/O module to be replaced represents the
value 0, the PROFIsafe address of the replacement I/O module must be set using
the parameterization tool (see section "Commissioning" > ... > "Parameterization
of the PROFIsafe I/O Module with the WAGO Parameterization Tool"). In
addition to setting the PROFIsafe address, also configure the replacement I/O
module using the WAGO parameterization tool (see section "Commissioning"
> ... > "Parameterization of the PROFIsafe I/O Module with the WAGO
Parameterization Tool").
Determine the PROFIsafe address if the coding switch is set to "0"!
You can use the WAGO parameterization tool to read the current PROFIsafe
address from the PROFIsafe I/O module to be replaced.
Pos: 57 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Version 1.4.0, valid from HW/SW Version 01/02
Manual