Parameter Short-Circuit Test Ix; Table 33: Input /Clock Output Assignment - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

82
Commissioning
Pos: 48.7 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Parametrieren mit WAGO-I/O-CHECK/Parametrieren 750-66x/Parameter Kurzschlusstest 750-066x/000-003 (4 DI) @ 6\mod_1264755492944_21.docx @ 48918 @ 4 @ 1
8.3.4.2

Parameter Short-Circuit Test Ix

Protect signal lines when installing!
When connecting signal lines to the digital inputs of the PROFIsafe I/O module,
make sure that only the following signals are transmitted within a cable or non-
metallic sheathed cable:
Those whose short-circuit does not lead to a dangerous failure of the safety
function
Those supplied by different clock outputs
Therefore, please make sure that the signal lines are installed in accordance with
EN 60204-1 or EN ISO 13849-2 (e.g., as separate sheathed lines or in separate
cable ducts).
The digital inputs are tested cyclically by the PROFIsafe I/O module. If the
Short-circuit test parameter is set to the "not active" value, then the PROFIsafe
I/O module only tests the input circuit for internal errors. You have to set the
Short-circuit test parameter to "not active" if, for example, you connect the
semiconductor output of a sensor (such as light arrays, light barriers, etc.) to the
digital input of the PROFIsafe I/O module.
If you set the Short-circuit test parameter to the "active" value, then you have to
connect the digital input to the associated clock output via a switching element
(e.g., break contact). By doing so, the PROFIsafe I/O module tests the signal line
for short circuits against external voltages. If the short circuit test detects an
external voltage on the digital input, the PROFIsafe I/O module is passivated and
the "Short circuit" diagnostic message is output to the safe PLC.

Table 33: Input /Clock Output Assignment

Inputs
I1, I3
I2, I4
Using the cyclical tests of the digital inputs, the PROFIsafe I/O module detects the
following errors on the digital inputs:
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Associated Clock Output (for Activated Short-Circuit Test)
Version 1.4.0, valid from HW/SW Version 01/02
WAGO-I/O-SYSTEM 750
T1
T2
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wago-i/o-system 753-661/000-003

Table of Contents