Typical Response Time Of The Digital Inputs In An Error-Free Case; Table 24: Safe Response Time Of The Digital Inputs - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
4.6.9.2

Typical Response Time of the Digital Inputs in an Error-free Case

Only use response times in the event of a failure for the safety response time!
To prevent any personal injury or property damage, only use the values of the safe
response time for errors for defining the safety response time (see Section "Safe
Response Times for Digital Inputs in the Event of an Error"). Under no
circumstances may you use the response times for the digital inputs during error-
free operation for the design!
The following table lists the typical response times for the digital inputs in error-
free operation.
Table 24: Safe Response Time of the Digital Inputs in the Error-Free Operation
Signal
change
Input
filter time
0 ms
0.5 ms
1 ms
2 ms
3 ms
5 ms
10 ms
20 ms
50 ms
100 ms
200 ms
Pos: 24.38 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Standard Operating Mode
Single-Channel
Evaluation
Analysis
Equivalent
0  1
1  0
0  1
15 ms
15 ms
15 ms
17 ms
17 ms
17 ms 9.5 ms 17 ms 9.5 ms 17 ms
19 ms
19 ms
19 ms
21 ms
21 ms
21 ms
25 ms
25 ms
25 ms
33 ms
33 ms
33 ms
53 ms
53 ms
53 ms
93 ms
93 ms
93 ms
211 ms 211 ms 211 ms 59 ms 211 ms 59 ms 211 ms 211 ms
411 ms 411 ms 411 ms 109 ms 411 ms 109 ms 411 ms 411 ms
808 ms 808 ms 808 ms 209 ms 808 ms 209 ms 808 ms 808 ms
Valence
Valence
Evaluation
Antivalent
1  0
0  1
9 ms
15 ms
10 ms
19 ms
11 ms
21 ms
12 ms
25 ms
13 ms
33 ms
19 ms
53 ms
29 ms
93 ms
Device Description
Rotary Table
Operating
Mode
1  0
0  1
1  0
9 ms
15 ms
15 ms
17 ms
10 ms
19 ms
19 ms
11 ms
21 ms
21 ms
12 ms
25 ms
25 ms
13 ms
33 ms
33 ms
19 ms
53 ms
53 ms
29 ms
93 ms
93 ms
43