Parameterization Status Profisafe; Profisafe Parameterization Fault - WAGO I/O SYSTEM 750 750-833 Manual

Modular i/o-system profibus dp/v1, programmable field bus controller
Table of Contents

Advertisement

100 •
Programmable Field Bus Controller 750-833
Diagnostics

3.9.7 Parameterization Status PROFIsafe

During start up of the DP Master, the PROFIsafe I/O modules receive the
F-parameter data that is saved by a 16-bit CRC and is used to initialize the
F-profile driver. If the parameterization failed, the F-profile driver will not be
started in the F-I/O modules. The field bus coupler indicates the cause of the
error via a status message (parameterization status).
The parameterization status is structured as follows:
Byte
22
23
24
25
26
3.9.7.1

PROFIsafe Parameterization Fault

PROFIsafe Parameterization Fault
Fault Number
Information
7
6
5
4
2
2
2
2
0
0
0
0
1
0
0
0
Slot
0
0
0
0
Fault number
Meaning
Set PROFIsafe address does not agree with the parameterized
64
(0x40)
dez
F_DESTINATION_ADDR
Invalid parameterization of the F_DESTINATION_ADDR. The
65
(0x41)
dez
addresses 0x0000 and 0xFFFF are invalid.
Invalid parameterization of the F_SOURCE_ADDR. The addresses
66
(0x42)
dez
0x0000 and 0xFFFF are invalid.
Invalid parameterization of the F_WDG_TIME. A monitoring time of
67
(0x43)
dez
0 ms is invalid.
Invalid parameterization of the F_SIL. The required SIL class cannot
68
(0x44)
dez
be supported by the F-Module.
Invalid parameterization of the F_CRC_LENGTH. The required CRC
69
(0x45)
dez
length does not correspond to the generated one of the F-Module.
Invalid F-Parameter set version. The requested version does not
70
(0x46)
dez
correspond to the status of the F-Module.
The CRC, which was determined by the F module via the PROFIsafe
71
(0x47)
parameters (CRC1), varies from the CRC1 transmitted in the
dez
parameterization telegram.
72
(0x48)
Reserved fault numbers, which are not allowed to be used or
dez
evaluated.
73
(0x49)
dez
Meaning
3
2
1
0
2
2
2
2
Header byte
0
1
0
1
(5 byte status information incl. header)
Status type = status message
0
0
0
1
PROFIsafe I/O module slot
(range of values 2 ... 64)
Status differentiation = none
0
0
0
0
PROFIsafe status message
(range of values 64 ... 71)