Table 34: Error Detection

Error, Example
(x = 1 ... 4, m = 1.2)
Short circuit I1 / I2
Short circuit I3 / I4
Short circuit Ix / +24 V
Short circuit Ix / GND
Short circuit Tm / +24 V
Short circuit Tm / GND
Short circuit T1 / T2
Internal error in input circuit
No supply voltage
* Only if the clock outputs are connected to the digital inputs.
Pos: 48.8 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Parametrieren mit WAGO-I/O-CHECK/Parametrieren 750-66x/Hinweis: Parameter Kurzschlusstest Ix, Verhalten im Fehlerfall ohne Leistungsausgänge @ 7\mod_1272292760831_21.docx @ 55730 @ @ 1
Behavior of the PROFIsafe I/O module in the event of a failure
If an error is detected on a digital input by the PROFIsafe I/O module, the entire
PROFIsafe I/O module is passivated by the process image of all digital inputs
being set to "0".
For detailed information, read the section "Diagnostics".
Pos: 48.9 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Error Detection
Short-Circuit Test
"Active"
Yes
Yes
Yes
No
Yes*
Yes
Yes*
Yes
Yes
Commissioning
83
Short-Circuit Test
"Not Active"
No
No
No
No
No
Yes
No
Yes
Yes