Ipar Server; Figure 3: Ipar Server; Table 3: Legend For The Ipar Server Figure - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

18
PROFIsafe
3.1

iPar Server

The iPar parameters are used to configure device functions of a safe device such
as the PROFIsafe I/O modules of the WAGO-I/O-SYSTEM 750/753. The
"WAGO Safety Editor 75x" parameterization tool (SEDI) can be used to set the
individual parameters of WAGO PROFIsafe I/O modules. SEDI is the CPD tool
for WAGO PROFIsafe I/O modules.

Figure 3: iPar Server

Table 3: Legend for the iPar Server Figure

No. Explanation
1
Instantiation of the iPar Server function
2
CPD Tool Start and parameter transfer (e.g., node address)
3
Parameterization of individual module parameters (iPar) and
commissioning; test and release
4
Transfer of iPar signature (CRC via the individual parameters) to the F-Host
5
During start-up, transfer of the signature to F-slave (Prm_Telegram)
6
Message to iPar server about diagnostic agent (alarm/status)
7
iPar server polls Diag FB and starts "Save" if required
8
iPar server polls Diag FB and starts "Restore" if required
It is often required during a repair to quickly replace a device without using
additional manufacturer tools for parameterization of the device functions.
To meet this requirement, the iPar server is used that offers appropriate services
for saving and restoring individual parameters. The "iPar Server" is available as a
WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Version 1.4.0, valid from HW/SW Version 01/02