I/O Module With Ipar Server Functionality; Profisafe Address Set Using The Coding Switch; Profisafe Address Set Using The Parameterization Tool; I/O Module Without Ipar Server Functionality - WAGO 750-666/000-003 Manual

Wago-i/o-system 750 4fdi/2fdo 24v/10a profisafe v2 ipar, 4-channel digital input and 2-channel digital output module profisafe v2 ipar, 24v/10a semiconductor power output
Hide thumbs Also See for 750-666/000-003:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
10.1.2

I/O Module with iPar Server Functionality

10.1.2.1

PROFIsafe Address Set Using the Coding Switch

If the PROFIsafe address of the I/O module to be replaced is set using the coding
switch on the side, i.e., the switch setting does not equal 0, proceed with replacing
the I/O module as follows:
Acknowledge the PROFIsafe communication error in the safe PLC.
After acknowledging the error, the replacement I/O module automatically requests
its individual parameters from the iPar server. The safety-related verification of
these parameters occurs in the PROFIsafe I/O module. If the verification step is
unsuccessful, the replacement I/O module sends a second request to the iPar
server. If the process cannot be completed successfully, the replacement I/O
module remains in its initial state and must be configured using the WAGO
parameterization tool (see section "Parameterization of the PROFIsafe I/O
Module with the WAGO Parameterization Tool").
10.1.2.2

PROFIsafe Address Set Using the Parameterization Tool

If the setting of the coding switch of the I/O module to be replaced represents the
value 0, the PROFIsafe address of the I/O module to be replaced must be set using
the parameterization tool (see section "Parameterization of the PROFIsafe I/O
Module with the WAGO Parameterization Tool"). After successfully setting the
PROFIsafe address, proceed as follows:
Acknowledge the PROFIsafe communication error in the safe PLC.
After acknowledging the error, the replacement I/O module automatically requests
its individual parameters from the iPar server. The safety-related verification of
these parameters occurs in the PROFIsafe I/O module. If the verification step is
unsuccessful, the replacement I/O module sends a second request to the iPar
server. If the process cannot be completed successfully, the replacement I/O
module remains in its initial state and must be configured using the WAGO
parameterization tool (see section "Parameterization of the PROFIsafe I/O
Module with the WAGO Parameterization Tool").
10.1.3

I/O Module without iPar Server Functionality

10.1.3.1
PROFIsafe Address Set Using the Coding Switch
If the PROFIsafe address of the I/O module to be replaced is set using the coding
switch, i.e., the switch setting does not equal 0, use the WAGO parameterization
tool to configure the replacement I/O module (see section "Parameterization of the
PROFIsafe I/O Module with the WAGO Parameterization Tool").
10.1.3.2

PROFIsafe Address Set Using the Parameterization Tool

If the setting of the coding switch of the I/O module to be replaced represents the
value 0, the PROFIsafe address of the replacement I/O module must be set using
the parameterization tool (see section "Parameterization of the PROFIsafe I/O
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Service
133