Variant 2: User Acknowledgement Via "Oa_Req" And "F_Ack; Figure 36: Schematic Representation For User Acknowledgement Via "Oa_Req" And "F_Ack - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
9.3.2
Variant 2: User Acknowledgement via "OA_Req" and
"F_Ack"
For safe PLCs that offer the safe application no access to the "OA_Req", only
PROFIsafe communication errors can be acknowledged via the "OA_Req" bit in
the PROFIsafe control byte. To acknowledge other errors, the PROFIsafe I/O
module provides an acknowledgement via the "F_Ack" in the output process data.
For this variant, the acknowledgement request is only displayed for PROFIsafe
communication errors by the PROFIsafe status display element to the PROFIsafe
I/O module. For other errors, the acknowledgement request is not displayed by the
PROFIsafe status display element. The acknowledgement request for these errors
is only displayed by the group error display element (red) and channel status (red)
of the PROFIsafe I/O module.
To acknowledge both PROFIsafe communication errors and other errors with one
button, the "User Acknowledgement" signal must affect the "OA_Req" and
"F_Ack" bits. The figure below provides a schematic representation of this variant
for user acknowledgement.

Figure 36: Schematic Representation for User Acknowledgement via "OA_Req" and "F_Ack"

Pos: 54 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Diagnostics
105