WAGO -I/O-SYSTEM 750 Series Manual page 87

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Behavior of the PROFIsafe I/O module during discrepancy time errors at
several input pairs
If a discrepancy error is detected by the PROFIsafe I/O module at several input
pairs, the module passivates all of the digital inputs. Depending on the setting of
the Restart barrier parameter, you can acknowledge the reported error(s) and
any diagnosis without or after eliminating the cause of the error for all affected
input pairs (see Section "Restart Barrier Ix & Ix+1" Parameter).
Pos: 48.14 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Commissioning
87