Service

Pos: 55 /Alle Serien (Allgemeine Module)/Überschriften für alle Serien/Service (Wartung)Service - Überschrift 1 @ 4\mod_1241771948421_21.docx @ 32830 @ 1 @ 1
10
Service
Pos: 56 /Serie 750 (WAGO-I/O-SYSTEM)/Service/PROFIsafePROFIsafe-Busklemme austauschen @ 7\mod_1265809189196_21.docx @ 50260 @ 23344344 @ 1
10.1

Replacing a PROFIsafe I/O Module

Replacing a PROFIsafe I/O module with a PROFIsafe I/O module of the same
type is described in the following.
Replacing a PROFIsafe I/O module with an I/O module of another type is always
associated with a new project design (see section "Commissioning" > ... >
"Programming the Safe PLC").
10.1.1

Procedure

When replacing a PROFIsafe I/O module, first perform the following steps:
Switch off the supply voltage of the fieldbus node in which the I/O module
to be replaced is found.
Pull the I/O module to be replaced out of the fieldbus node (see section
"Mounting" > ... > "Inserting and Removing Devices").
Read the PROFIsafe address on the coding switch of the I/O module to be
replaced and apply this setting to the replacement I/O module.
Plug the replacement I/O module into the position of the I/O module to be
replaced in the fieldbus node.
Switch on again the supply voltage of the fieldbus node concerned.
Then perform the one of the following steps based on your system configuration:
If the setting of the coding switch of the I/O module to be replaced has a
value not equal to 0 and it is operated with iPar server functionality,
continue reading in section "Service" > ... > "PROFIsafe Address Set Using
the Coding Switch".
If the setting of the coding switch of the I/O module to be replaced has a
value equal to 0 and it is operated with iPar server functionality, continue
reading in section "Service" > ... > "PROFIsafe Address Set Using the
Parameterization Tool".
If the setting of the coding switch of the I/O module to be replaced has a
value not equal to 0 and it is not operated with iPar server functionality,
continue reading in section "Service" > ... > "PROFIsafe Address Set Using
the Parameterization Tool".
If the setting of the coding switch of the I/O module to be replaced has a
value equal to 0 and it is not operated with iPar server functionality,
continue reading in section "Service" > ... > "PROFIsafe Address Set Using
the Coding Switch".