WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
10.1.2

I/O Module with iPar Server Functionality

10.1.2.1

PROFIsafe Address Set Using the Coding Switch

If the PROFIsafe address of the I/O module to be replaced is set using the coding
switch on the side, i.e., the switch setting does not equal 0, proceed with replacing
the I/O module as follows:
Acknowledge the PROFIsafe communication error in the safe PLC.
After acknowledging the error, the replacement I/O module automatically requests
its individual parameters from the iPar server. The safety-related verification of
these parameters occurs in the PROFIsafe I/O module. If the verification step is
unsuccessful, the replacement I/O module sends a second request to the iPar
server. If the process cannot be completed successfully, the replacement I/O
module remains in its initial state and must be configured using the WAGO
parameterization tool (see section "Commissioning" > ... > "Parameterization of
the PROFIsafe I/O Module with the WAGO Parameterization Tool").
10.1.2.2

PROFIsafe Address Set Using the Parameterization Tool

If the setting of the coding switch of the I/O module to be replaced represents the
value 0, the PROFIsafe address of the I/O module to be replaced must be set using
the parameterization tool (see section "Commissioning" > ... > "Parameterization
of the PROFIsafe I/O Module with the WAGO Parameterization Tool"). After
successfully setting the PROFIsafe address, proceed as follows:
Acknowledge the PROFIsafe communication error in the safe PLC.
After acknowledging the error, the replacement I/O module automatically requests
its individual parameters from the iPar server. The safety-related verification of
these parameters occurs in the PROFIsafe I/O module. If the verification step is
unsuccessful, the replacement I/O module sends a second request to the iPar
server. If the process cannot be completed successfully, the replacement I/O
module remains in its initial state and must be configured using the WAGO
parameterization tool (see section "Commissioning" > ... > "Parameterization of
the PROFIsafe I/O Module with the WAGO Parameterization Tool").
10.1.3

I/O Module without iPar Server Functionality

10.1.3.1
PROFIsafe Address Set Using the Coding Switch
If the PROFIsafe address of the I/O module to be replaced is set using the coding
switch, i.e., the switch setting does not equal 0, use the WAGO parameterization
tool to configure the replacement I/O module (see section "Commissioning"
> ... > "Parameterization of the PROFIsafe I/O Module with the WAGO
Parameterization Tool").
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Service
107