Table 23: Safe Response Time Of The Digital Inputs - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

42
Device Description
The following table lists the safe response times in the event of failure that result
from the input filter time set.
Table 23: Safe Response Time of the Digital Inputs in the Event of Failure
Input
Filter Time
0 ms
0.5 ms
1 ms
2 ms
3 ms
5 ms
10 ms
20 ms
50 ms
100 ms
200 ms
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Standard Operating Mode
Single-
Valence
Channel
Evaluation
Analysis
Equivalent
35 ms
35 ms
36 ms
36 ms
38 ms
38 ms
42 ms
42 ms
47 ms
47 ms
59 ms
59 ms
89 ms
89 ms
150 ms
150 ms
331 ms
331 ms
633 ms
633 ms
1237 ms
1237 ms
Version 1.4.0, valid from HW/SW Version 01/02
WAGO-I/O-SYSTEM 750
Rotary Table
Valence
Operating
Evaluation
Mode
Antivalent
19 ms
35 ms
20 ms
36 ms
21 ms
38 ms
24 ms
42 ms
28 ms
47 ms
36 ms
59 ms
56 ms
89 ms
96 ms
150 ms
217 ms
331 ms
419 ms
633 ms
821 ms
1237 ms
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wago-i/o-system 753-661/000-003

Table of Contents