Single-Channel Safety Application, Proof Test Interval 10 Years; Table 17: Safety Parameters For Single-Channel Safety Application - 10 Years - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

38
Device Description
4.6.6.3

Single-channel Safety Application, Proof Test Interval 10 Years

Table 17: Safety Parameters for Single-Channel Safety Application – 10 Years
Maximum safety integrity level
acc. EN 62061
Maximum safety integrity level
acc. IEC 61508
Maximum performance level
acc. EN ISO 13849-1
Proof test interval/usage duration
Probability of failure
*)
PFD
,
Proof test interval
10 years
(low demand mode)
(IEC 61508)
Probability of failure
*)
PFH
,
Proof test interval
10 years
(high demand mode)
(IEC 61508)
Hardware fault tolerance HFT with single-
channel application
(IEC 61508 / EN ISO 13849-1)
DC (diagnostic coverage level)
MTTF
d
(Mean Time To Failure dangerous)
*)
PFD: Probability of a dangerous failure on demand
PFH: Probability of a dangerous failure per hour
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
for 1 input (input to
fieldbus)
for 4 inputs (inputs
to fieldbus)
for 1 input (input to
fieldbus)
for 4 inputs (inputs
to fieldbus)
Version 1.4.0, valid from HW/SW Version 01/02
WAGO-I/O-SYSTEM 750
SIL2
SIL2
Cat. 2/PL d
10 years
-5
8.09 × 10
(0.81 % of all PFD from
-2
10
at SIL2)
-4
1.00 × 10
(1.00 % of all PFD from
-2
10
at SIL2)
-9
1.85 × 10
(0.19 % of all PFH from
-6
10
at SIL2)
-9
2.30 × 10
(0.23 % of all PFH from
-6
10
at SIL2)
0 (1 error in the application can lead
to a failure of the safety equipment)
95 %
> 100 years
Manual