98
Service
If the coding switch setting of the F I/O module to be replaced has a value
other than 0 and this F I/O module is operated without iPar server
functionality, read section "Service" > "Replacing the F I/O Module" > "F I/O
Module without iPar Server Functionality" > "PROFIsafe Address Set Using
the Coding Switch."
If the coding switch setting of the F I/O module to be replaced has a value
of 0 and this F I/O module is operated without iPar server functionality, read
section "Service" > "Replacing the F I/O Module" > "F I/O Module without
iPar Server Functionality" > "PROFIsafe Address Set Using the
Parameterization Tool."
9.1.2

F I/O Module with iPar Server Functionality

9.1.2.1

PROFIsafe Address Set Using the Coding Switch

If the PROFIsafe address of the F I/O module to be replaced is set using the
coding switch on the side, i.e., the switch setting does not equal 0, proceed as
follows afterwith replacing the F I/O module:
After start-up, the replacement module automatically requests its individual
parameters from the iPar server. The safety-related verification of these
parameters occurs in the F I/O module. If the verification step is unsuccessful, the
replacement module sends a second request to the iPar server. If the process
cannot be completed successfully, the replacement module remains in its initial
state and must be configured using the WAGO parameterization tool (see
Section "Service" > "Replacing the F I/O Module" > "F I/O Module without iPar
Server Functionality" > "PROFIsafe Address Set Using the Coding Switch").
When using the WAGO iPar server functionality, follow the procedure found in
the corresponding application note.
9.1.2.2

PROFIsafe Address Set Using the Parameterization Tool

If the coding switch of the F I/O module to be replaced is set to 0, the PROFIsafe
address of the replacement module must be set through the parameterization
tool (see section "Commissioning" > ... > "Parameterization of the F I/O Module
with the WAGO Parameterization Tool"). The PROFIsafe address must be set to
the value of the previous module. You can find the correct address in the system
documentation. After successfully setting the PROFIsafe address, proceed as
follows:
After start-up, the replacement module automatically requests its individual
parameters from the iPar server. The safety-related verification of these
parameters occurs in the F I/O module. If the verification step is unsuccessful, the
replacement module sends a second request to the iPar server. If the process
cannot be completed successfully, the replacement module remains in its initial
state and must be configured using the WAGO parameterization tool (see section
"Service" > "Replacing the F I/O Module" > "F I/O Module without iPar Server
Functionality" > "PROFIsafe Address Set Using the Parameterization Tool").
Manual