Diagnostics

Table 38: Diagnostic Messages

Alarm
Differing
F_Dest_Add
Discrepancy time
exceeded
Incorrect
F_CRC_Length
Incorrect
F_Par_Version
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Diagnostic
Module Diagnostics
type
Coding
0x0040
LED
Group error (E) red
indication
PROFIsafe (G) red
The PROFIsafe address assigned as part of
the F parameterization differs from that set
Solution
on the F I/O module.. Check the DIP
switch setting or PROFIsafe address set
using the safety editor (SEDI).
Diagnostic
Channel Diagnostics
type
Coding
0x021E
LED
Status In (A, B, C or D) red,
indication
group error (E) red
For dual channel evaluation of the input
pair, the F I/O module has determined that
the discrepancy time set has been
Solution
exceeded. Check the connected contacts.
Adjust the discrepancy time setting if
necessary.
Diagnostic
Module Diagnostics
type
Coding
0x0045
LED
Group error (E) red
indication
PROFIsafe (G) red
The configured F_CRC length is not
possible in the current operating mode.
Solution
Observe the dependency between
F_Par_Version and F_CRC_Length and
select a valid combination.
Diagnostic
Module Diagnostics
type
Coding
0x0046
LED
Group error (E) red
indication
PROFIsafe (G) red
The set version of the F parameter set is
incorrect. Observe the dependency
Solution
between F_Par_Version and
F_CRC_Length and select a valid
combination.
Version 1.4.0, valid from HW/SW Version 01/02
WAGO-I/O-SYSTEM 750