WAGO -I/O-SYSTEM 750 Series Manual page 100

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

100
Diagnostics
Table 38: Diagnostic Messages
Alarm
Short circuit on T1
Short circuit on T2
Non-supported
F_Block_ID
Non-supported
F_SIL
Safety-oriented
tripping
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Diagnostic
Module Diagnostics
type
Coding
0x020B
LED
Group error (E) red
indication
Clock output T1 of the F I/O module has
short circuited with the 0V potential of the
Solution
field supply. Check the clock output
wiring.
Diagnostic
Module Diagnostics
type
Coding
0x020C
LED
Group error (E) red
indication
Clock output T2 of the F I/O module has
short circuited with the 0V potential of the
Solution
field supply. Check the clock output
wiring.
Diagnostic
Module Diagnostics
type
Coding
0x004C
LED
Group error (E) red
indication
PROFIsafe (G) red
The F parameter block signaled by the
F_Block_ID is not supported by the F I/O
Solution
module. Use an F parameter block
supported by the F I/O module.
Diagnostic
Module Diagnostics
type
Coding
0x0044
LED
Group error (E) red
indication
PROFIsafe (G) red
The F I/O module cannot be operated in
Solution
the configured SIL. Correct the F
parameterization.
Diagnostic
Module Diagnostics
type
Coding
0x0219
LED
Group error (E) red, 2 Hz flashing
indication
The F I/O module has taken the safe state
and switched off the outputs. Immediately
Solution
replace the F I/O module and return it to
WAGO Kontakttechnik GmbH & Co. KG
for fault analysis.
Version 1.4.0, valid from HW/SW Version 01/02
WAGO-I/O-SYSTEM 750
Description
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wago-i/o-system 753-661/000-003

Table of Contents