Emergency Off Connection, Dual Channel, Equivalent Evaluation; Figure 31: Connection 2 X Emergency-Off Switch, Dual Channel - WAGO -I/O-SYSTEM 750 Series Manual

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
7.3.1.2

Emergency Off Connection, Dual channel, Equivalent Evaluation

Pos: 40.8 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiele 750-066x/000-003 Warnung: Geschützte Verlegung bei Kurzschlusst. „nicht aktiv" be @ 7\mod_1267016745817_21.docx @ 51400 @ @ 1
Pay attention to the protected installation of signal lines during short circuit
test "inactive"!
If you have set the Short circuit test parameter of an input to "inactive", the
signal lines must be installed protected among each other and between the sensors
and inputs according to EN 60204-1 or EN ISO 13849-2 (e.g., as separate
sheathed lines or in separate cable ducts).
Pos: 40.9 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiele 750-066x/000-003 Warnung: Geschützte Verlegung bei aktiviertem Kurzschlusstest! @ 7\mod_1267016960910_21.docx @ 51403 @ @ 1
Pay attention to the protected installation when the short circuit test is
activated!
With the two clock outputs T1 and T2, you must install the signal lines from
maximum two contiguous input channels in one common cable. Otherwise, the
PROFIsafe I/O module cannot detect short circuits between signal lines of the
inputs that are tested with the same clock output. Make sure that the signal lines
that belong to the same clock output T1 or T2 are installed protected against each
other and between the safe sensors according to EN 60204-1 or EN ISO 13849-2
(e.g., as separate sheathed lines or in separate cable ducts).
Pos: 40.10 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiele 750-066x/000-003 Warnung: Alternative Maßnahmen zur Fehleraufdeckung @ 23\mod_1439813218651_21.docx @ 189528 @ @ 1
Alternative measures for fault detection!
You can take alternative measures (e.g., antivalent evaluation) for fault detection
to achieve the required risk reduction for your application (e.g., SIL3/Cat.4/PL e).
The safety parameters of the PROFIsafe I/O module do not change.
Pos: 40.11 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiel 750-0661/000-003 Bild 2 x Not-Aus, zweikanalig @ 7\mod_1266331320479_21.docx @ 50774 @ @ 1
Figure 31: Connection 2 x Emergency-Off Switch, Dual Channel, Equivalent Evaluation
Pos: 40.12 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiel 750-066x/000-003 Text Not-Aus, zweikanalig @ 7\mod_1269942078421_21.docx @ 54702 @ @ 1
For emergency off applications that require single fault security, you can connect
two digital inputs via two switching elements (two-channel emergency off
switches with two break contacts) to the PROFIsafe I/O module.
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Connect Devices
65