WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Behavior when group error LED (LED E) is flashing
A flashing group error LED (LED E) indicates that the PROFIsafe I/O module
has detected an internal safety critical error. The cause can be a defect in the
PROFIsafe I/O module or an environmental EMC error. In this case, switch off
the PROFIsafe I/O module completely and the switch it back on.
If the problem occurs several times, it points to a defect in the PROFIsafe I/O
module. In this case, return the PROFIsafe I/O module to WAGO Kontakttechnik
GmbH & Co. KG for fault analysis.
Pos: 24.22 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Device Description
29