WAGO -I/O-SYSTEM 750 Series Manual page 101

4fdi 24v profisafe v2 ipar safety 4-channel digital input module profisafe v2
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-661/000-003 4FDI 24V PROFIsafe V2 iPar
Table 38: Diagnostic Messages
Alarm
Invalid
iParameters
Invalid iParam.
from iPar server
Invalid F_CRC1
Invalid
F_Dest_Add
Invalid
F_Source_Add
Manual
Version 1.4.0, valid from HW/SW Version 01/02
Diagnostic
Module Diagnostics
type
Coding
0x0200
LED
Group error (E) red,
indication
parameterization (H) red, 1 Hz flashing
The individual parameter set for the F I/O
module is inconsistent. Correct the
Solution
parameterization taking into account
dependencies between individual settings.
Diagnostic
Module Diagnostics
type
Coding
0x004B
LED
Group error (E) red,
indication
parameterization (H) red, 1 Hz flashing
The individual parameter set for the F I/O
module provided by the iPar server are
Solution
inconsistent. Make sure that a valid
iParameter set exists on the iPar server.
Check fieldbus transmission if necessary.
Diagnostic
Module Diagnostics
type
Coding
0x0047
LED
Group error (E) red
indication
PROFIsafe (G) red
The F_CRC1 form from the F parameter
Solution
set is invalid. Create a consistent F
parameter set.
Diagnostic
Module Diagnostics
type
Coding
0x0041
LED
Group error (E) red
indication
The PROFIsafe address of the F I/O
Solution
module must lie within the range of 1 to
65534. Correct the F parameterization.
Diagnostic
Module Diagnostics
type
Coding
0x0042
LED
Group error (E) red
indication
PROFIsafe (G) red
The PROFIsafe address of the F host must
Solution
lie within the range of 1 to 65534. Correct
the F parameterization.
Diagnostics
Description
101

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wago-i/o-system 753-661/000-003

Table of Contents