Parameter Descriptions

4.15 Parameters: 16-** Data Readouts

4.15.1 16-0* General Status
16-00 Control Word
Range:
0
[0 - 65535 ] View the control word sent from the frequency
*
4
4
16-01 Reference [Unit]
Range:
0 ReferenceFeed-
backUnit
*
16-02 Reference [%]
Range:
0 %
[-200 -
*
200 %]
16-03 Status Word
Range:
0
[0 - 65535 ] View the status word sent from the frequency
*
16-05 Main Actual Value [%]
Range:
0 %
[-200 - 200 %] View the 2-byte word sent with the status
*
16-09 Custom Readout
Range:
0 CustomRea-
doutUnit
*
108
VLT
Function:
converter via the serial communication port in
hex code.
Function:
[-4999 - 4999
View the present reference
ReferenceFeed-
value applied on impulse
backUnit]
or analog basis in the unit
resulting from the configu-
ration selected in
parameter 1-00 Configu-
ration Mode.
Function:
View the total reference. The total reference
is the sum of digital, analog, preset, bus,
and freeze references, plus catch up and
slow down.
Function:
converter via the serial communication port in
hex code.
Function:
word to the bus master reporting the
main actual value.
Function:
[0 - 9999
View the custom readout from
CustomRea-
parameter 0-30 Custom
doutUnit]
Readout Unit to
parameter 0-32 Custom
Readout Max Value.
Danfoss A/S © 06/2017 All rights reserved.
®
AutomationDrive FC 360
4.15.2 16-1* Motor Status
16-10 Power [kW]
Range:
0 kW
[0 -
*
1000
kW]
16-11 Power [hp]
Range:
0 hp
[0 -
*
1000 hp]
16-12 Motor Voltage
Range:
0 V
[0 - 65535 V] View the motor voltage. A calculated value
*
16-13 Frequency
Range:
0 Hz
[0 - 6553.5 Hz] View the motor frequency, without
*
16-14 Motor current
Range:
0 A
[0 - 655.35
*
A]
16-15 Frequency [%]
Range:
0 %
[0 -
*
6553.5 %]
Function:
Shows motor power in kW. The calculated
value shown is based on the actual motor
voltage and motor current. The value is filtered,
and therefore approximately 300 ms may pass
from when an input value changes to when
the data readout values change. The resolution
of readout value on fieldbus is in 10 W steps.
Function:
View the motor power in hp. The value shown
is calculated on the basis of the actual motor
voltage and motor current. The value is
filtered, and therefore approximately 300 ms
may pass from when an input value changes
to when the data readout values change.
Function:
is used for controlling the motor.
Function:
resonance dampening.
Function:
View the motor current measured as an
average value, I
. The value is filtered, and
RMS
approximately 200 ms may pass from when
an input value changes to when the data
readout values change.
Function:
View a 2-byte word reporting the actual
motor frequency (without resonance
dampening) as a percentage (scale
0000-4000 hex) of parameter 4-19 Max
Output Frequency.
MG06C702