Parameter Descriptions
When parameter 1-10 Motor Construction is set to options
that enable permanent motor mode, the only option
available is [1] Enable Complete AMA.
Activate the AMA function by pressing [Hand On] after
selecting [1] Enable Complete AMA or [2] Enable Reduced
AMA. After a normal sequence, the display reads: Press [OK]
to finish AMA. After pressing [OK], the frequency converter
4
4
is ready for operation.
NOTICE
•
For the best adaptation of the frequency
converter, run AMA on a cold motor.
•
AMA cannot be performed while the motor is
running.
NOTICE
Avoid generating external torque during AMA.
If an LC filter is used, set the frequency converter to run in
U/f control mode (recommended), or perform reduced
+
AMA in VVC
complete AMA.
4.2.4 1-3* Adv. Motor Data I
Set parameters for advanced motor data. The motor data
in parameters 1-30 to 1-39 must match the motor for
optimal performance. If the motor data is not known,
running an AMA is recommended.
1-30 Stator Resistance (Rs)
Range:
Size
related
9999.000
*
Ohm]
1-31 Rotor Resistance (Rr)
Range:
Size
[ 0 -
related
9999.000
*
Ohm]
38
mode. If an LC filter is not used, perform
Function:
NOTICE
[ 0.0 -
This parameter cannot be
adjusted while the motor is
running.
Set the stator resistance value. Enter
the value from a motor datasheet
or perform an AMA on a cold
motor.
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the rotor resistance value. Obtain
the value from a motor datasheet or
by performing an AMA on a cold
Danfoss A/S © 06/2017 All rights reserved.
®
VLT
AutomationDrive FC 360
1-31 Rotor Resistance (Rr)
Range:
1-33 Stator Leakage Reactance (X1)
Range:
Size
related
*
1-35 Main Reactance (Xh)
Range:
Size
related
*
1-37 d-axis Inductance (Ld)
Range:
Size
related
*
Function:
motor. The default setting is calculated
by the frequency converter from the
motor nameplate data.
Function:
NOTICE
[ 0.0 -
9999.000
This parameter cannot be
Ohm]
adjusted while the motor is
running.
Set the stator leakage reactance
value. Obtain the value from a motor
datasheet or perform an AMA on a
cold motor. The default setting is
calculated by the frequency converter
from the motor nameplate data.
Function:
NOTICE
[ 0.0 -
9999.00
This parameter cannot be adjusted
Ohm]
while the motor is running.
Set the main reactance of the motor using
1 of these methods:
•
Run an AMA on a cold motor.
The frequency converter
measures the value from the
motor.
•
Enter the X
Obtain the value from the motor
supplier.
•
Use the X
h
frequency converter establishes
the setting based on the motor
nameplate data.
Function:
NOTICE
[ 0 - 65535
mH]
This parameter cannot be
adjusted while the motor is
running.
Enter the value of the d-axis
inductance. Obtain the value from the
permanent magnet motor datasheet
or perform an AMA on a cold motor.
value manually.
h
default setting. The
MG06C702