Parameter Descriptions
When parameter 1-10 Motor Construction is set to options
that enable permanent motor mode, the only option
available is [1] Enable Complete AMA.
Activate the AMA function by pressing [Hand On] after
selecting [1] Enable Complete AMA or [2] Enable Reduced
AMA. After a normal sequence, the display reads: Press [OK]
to finish AMA. After pressing [OK], the frequency converter
4
4
is ready for operation.
NOTICE
For the best adaptation of the frequency
converter, run AMA on a cold motor.
AMA cannot be performed while the motor is
running.
NOTICE
Avoid generating external torque during AMA.
If an LC filter is used, set the frequency converter to run in
U/f control mode (recommended), or perform reduced
+
AMA in VVC
complete AMA.
4.2.4 1-3* Adv. Motor Data I
Set parameters for advanced motor data. The motor data
in parameters 1-30 to 1-39 must match the motor for
optimal performance. If the motor data is not known,
running an AMA is recommended.
1-30 Stator Resistance (Rs)
Range:
Size
related
9999.000
*
Ohm]
1-31 Rotor Resistance (Rr)
Range:
Size
[ 0 -
related
9999.000
*
Ohm]
38
mode. If an LC filter is not used, perform
Function:
NOTICE
[ 0.0 -
This parameter cannot be
adjusted while the motor is
running.
Set the stator resistance value. Enter
the value from a motor datasheet
or perform an AMA on a cold
motor.
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the rotor resistance value. Obtain
the value from a motor datasheet or
by performing an AMA on a cold
Danfoss A/S © 06/2017 All rights reserved.
®
VLT
AutomationDrive FC 360
1-31 Rotor Resistance (Rr)
Range:
1-33 Stator Leakage Reactance (X1)
Range:
Size
related
*
1-35 Main Reactance (Xh)
Range:
Size
related
*
1-37 d-axis Inductance (Ld)
Range:
Size
related
*
Function:
motor. The default setting is calculated
by the frequency converter from the
motor nameplate data.
Function:
NOTICE
[ 0.0 -
9999.000
This parameter cannot be
Ohm]
adjusted while the motor is
running.
Set the stator leakage reactance
value. Obtain the value from a motor
datasheet or perform an AMA on a
cold motor. The default setting is
calculated by the frequency converter
from the motor nameplate data.
Function:
NOTICE
[ 0.0 -
9999.00
This parameter cannot be adjusted
Ohm]
while the motor is running.
Set the main reactance of the motor using
1 of these methods:
Run an AMA on a cold motor.
The frequency converter
measures the value from the
motor.
Enter the X
Obtain the value from the motor
supplier.
Use the X
h
frequency converter establishes
the setting based on the motor
nameplate data.
Function:
NOTICE
[ 0 - 65535
mH]
This parameter cannot be
adjusted while the motor is
running.
Enter the value of the d-axis
inductance. Obtain the value from the
permanent magnet motor datasheet
or perform an AMA on a cold motor.
value manually.
h
default setting. The
MG06C702