Parameter Descriptions
4.1.2 0-1* Set-up Operations
Define and control the individual parameter set-ups.
The frequency converter has 2 parameter set-ups that can
be programmed independently of each other. This makes
the frequency converter flexible and able to solve
advanced control functionality problems, often saving the
cost of external control equipment. For example, the 2 set-
ups can be used to program the frequency converter to
operate according to 1 control scheme in 1 set-up (for
example, motor 1 for horizontal movement) and another
control scheme in another set-up (for example, motor 2 for
vertical movement). Alternatively, they can be used by an
OEM machine builder to program all their factory-fitted
frequency converters for different machine types within a
range to have the same parameters and then during
production/commissioning simply select a specific set-up,
depending on which machine the frequency converter is
installed on.
The active set-up (that is, the set-up in which the
frequency converter is operating) can be selected in
parameter 0-10 Active Set-up and is shown in the LCP. By
selecting [9] Multi set-up, it is possible to switch between
set-ups with the frequency converter running or stopped,
via digital input or serial communication commands. If it is
necessary to change set-ups while running, ensure that
parameter 0-12 Link Setups is set as required. Use
parameter 0-11 Programming Set-up to edit parameters
within any of the set-ups while continuing the operation of
the frequency converter in its active set-up, which can be a
different set-up to that being edited. Use
parameter 0-51 Set-up Copy to copy parameter settings
between the set-ups to enable quicker commissioning if
similar parameter settings are required in different set-ups.
0-10 Active Set-up
Option:
Function:
Select the set-up in which the frequency converter
is to operate. Select parameter 0-51 Set-up Copy to
copy a set-up to 1 or all set-ups. To avoid
conflicting settings of the same parameter within
2 different set-ups, link the set-ups together in
parameter 0-12 Link Setups. Stop the frequency
converter before switching between set-ups where
the parameters marked Not changeable during
operation have different values. Parameters which
are Not changeable during operation are marked
FALSE in the parameter lists in chapter 5 Parameter
Lists.
[1]
Set-up
Set-up 1 is active.
*
1
[2]
Set-up
Set-up 2 is active.
2
[9]
Multi
This option is used for remote set-up selections
Set-up
via digital inputs and the serial communication
port. This set-up uses the settings from
parameter 0-12 Link Setups.
MG06C702
Programming Guide
0-11 Programming Set-up
Option:
[1]
Set-up 1
[2]
Set-up 2
[9]
Active
*
Set-up
0-12 Link Setups
Option:
[0]
Not
linked
[20]
Linked
*
0-14 Readout: Edit Set-ups / Channel
Range:
0
[-2147483647 -
*
2147483647 ]
0-16 Application Selection
Option:
[0]
None
*
[1]
Simple Process Close Loop
[2]
Local/Remote
[3]
Speed Open Loop
[4]
Simple Speed Close Loop
[5]
Multi Speed
Danfoss A/S © 06/2017 All rights reserved.
Function:
Select the set-up to be programmed during
operation; either the active set-up or the
inactive set-up. The set-up number being
edited flashes in the LCP.
[1] Set-up 1 to [2] Set-up 2 can be edited freely
during operation, independently of the active
set-up.
The set-up in which the frequency converter is
operating can also be edited during operation.
Function:
The link ensures synchronizing of the Not
changeable during operation parameter values
enabling shift from 1 set-up to another during
operation.
If the set-ups are not linked, a change between
them is not possible while the motor is running.
Thus the set-up change does not occur until the
motor is coasted.
Leave parameters unchanged in both set-ups
and cannot be changed while the motor is
running.
Copy Not changeable during operation
parameters from 1 set-up to the other, so they
are identical in both set-ups.
Function:
View the setting of
parameter 0-11 Programming Set-up. Edit
set-up for each communication channel. A
means active set-up; F means factory;
numbers indicate set-up code. Communi-
cation channels from right to left are LCP,
FC-bus, USB, and HPFB1-5.
Function:
Select integrated application
functions. When an application
is selected, a set of related
parameters are set automat-
ically.
4
4