Parameter Descriptions
21-21 Ext. 1 Proportional Gain
Range:
0.01
[0 - 10 ] The proportional gain indicates the number of
*
21-22 Ext. 1 Integral Time
Range:
4
4
10000 s
[0.01 -
*
10000 s]
21-23 Ext. 1 Differentation Time
Range:
0 s
[0 - 10 s] The differentiator does not react to a constant
*
21-24 Ext. 1 Dif. Gain Limit
Range:
5
[1 - 50 ] Set a limit for the differentiator gain (DG). The DG
*
114
VLT
Function:
times the error between the setpoint and the
feedback signal is to be applied.
Function:
The integrator provides an increasing
gain at a constant error between the
setpoint and the feedback signal. The
integral time is the time needed by the
integrator to reach the same gain as the
proportional gain.
Function:
error. It only provides a gain when the error
changes. The quicker the error changes, the
stronger the gain from the differentiator.
Function:
increases if there are fast changes. Limit the DG to
obtain a pure differentiator gain at slow changes
and a constant differentiator gain where quick
changes occur.
Danfoss A/S © 06/2017 All rights reserved.
®
AutomationDrive FC 360
MG06C702