Parameter Descriptions
5-40 Function Relay
Option:
[175] Running on
tension
4
4
[176] Ready to run
[193] Sleep Mode
[194] Broken Belt
Function
5-41 On Delay, Relay
Array [2](Relay 1 [0], Relay 2 [1])
Range:
0.01 s
[0 - 600 s] Enter the delay of the relay cutin time. The
*
Selected
Event
Relay
output
Selected
Event
Relay
output
Illustration 4.15 On Delay, Relay
5-42 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
0.01 s
[0 - 600 s]
*
66
®
VLT
Function:
parameter 37-00 Application Mode is set
to [2] Position Control.
Indicates whether tension PID control
is active (on) or inactive (off). This
option is only effective when
parameter 37-00 Application Mode is set
to [1] Center winder.
The center winder control is ready to
run. This option is only effective when
parameter 37-00 Application Mode is set
to [1] Center winder.
The frequency converter/system has
entered sleep mode. See parameter
group 22-4* Sleep Mode.
A broken belt condition has been
detected. See parameter group 22-4*
Sleep Mode.
Function:
relay only cuts in if the condition in
parameter 5-40 Function Relay is uninter-
rupted during the specified time.
On Delay
O Delay
P 5-41
P 5-42
On Delay
P 5-41
Function:
Enter the delay of the relay cutout time.
Danfoss A/S © 06/2017 All rights reserved.
AutomationDrive FC 360
Selected
Event
Relay
output
Illustration 4.16 Off Delay, Relay
If the selected event condition changes before the on- or
off delay timer expires, the relay output is unaffected.
On Delay
O Delay
P 5-41
P 5-42
MG06C702