Parameter Descriptions
Hz
P 4-14 Hz
High limit
P 1-23
Motor frequency
P 3-19
Jog speed
P 4-12 Hz
Low limit
t jog
P 3-80
Ramp up
(acc)
Illustration 4.11 Jog Ramp Time
t
  s  x n
  Hz
jog
s
Par .  3 − 80  =  
 Δ  jog speed  par .  3  −  19   Hz
3-81 Quick Stop Ramp Time
Range:
Function:
Size
[0.01 -
Enter the quick-stop ramp-down time,
related
3600 s]
which is the deceleration time from the
*
synchronous motor speed to 0 Hz. Ensure
that no resulting overvoltage occurs in the
inverter due to regenerative operation of
the motor required to achieve the given
ramp-down time. Ensure also that the
generated current required to achieve the
given ramp-down time does not exceed
the current limit (set in
parameter 4-18 Current Limit). Activate quick
stop with a signal on a selected digital
input, or via the serial communication port.
Hz
P 4-14 Hz
high limit
Reference
P 1-23
Motor frequency
P 4-12 Hz
low limit
Illustration 4.12 Quick Stop Ramp Time
MG06C702
Programming Guide
t jog
Time
P 3-80
Ramp down
(dec)
Time
P 3-81
Qramp
Qstop
Danfoss A/S © 06/2017 All rights reserved.
4.4.8 3-9* Digital Potentiometer
The digital potentiometer enables increase or decrease of
the actual reference by adjusting the set-up of the digital
inputs using the functions Increase, Decrease or Clear. To
activate the function, at least 1 digital input must be set to
Increase or Decrease.
3-90 Step Size
Range:
Function:
0.10 %
[0.01 -
Enter the increment size required for
200 %]
increase/decrease as a percentage of the
*
synchronous motor speed, n
decrease is activated, the resulting reference
is increased/decreased by the amount set in
this parameter.
3-92 Power Restore
Option: Function:
[0]
Off Reset the digital potentiometer reference to 0% after
*
power-up.
[1]
On
Restore the most recent digital potentiometer
reference at power-up.
3-93 Maximum Limit
Range:
Function:
100 %
[-200 -
Set the maximum permissible value for the
*
200 %]
resulting reference. This is recommended if
the digital potentiometer is used for fine-
tuning of the resulting reference.
3-94 Minimum Limit
Range:
Function:
-100 %
[-200 -
Set the minimum allowed value for the
200 %]
resulting reference. This is recommended if
the digital potentiometer is used for fine-
tuning of the resulting reference.
3-95 Ramp Delay
Range:
Function:
1000
[0 -
Enter the delay required from activation
ms
3600000 ms]
of the digital potentiometer function
*
until the frequency converter starts to
ramp the reference. With a delay of 0 ms,
the reference starts to ramp as soon as
increase/decrease is activated.
4
4
. If increase/
s
53