Parameter Descriptions
3-16 Reference 2 Source
Option:
4
4
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
*
[7]
Frequency input
29
[8]
Frequency input
33
[11] Local bus
reference
[20] Digital pot.meter
[32] Bus PCD
3-17 Reference 3 Source
Option:
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input
29
[8]
Frequency input
33
[11]
Local bus
*
reference
[20]
Digital pot.meter
[32]
Bus PCD
50
®
VLT
AutomationDrive FC 360
Function:
Select the reference input to be used
for the second reference signal.
Parameter 3-15 Reference 1 Source,
parameter 3-16 Reference 2 Source, and
parameter 3-17 Reference 3 Source define
up to 3 different reference signals. The
sum of these reference signals defines
the actual reference.
Function:
Select the reference input to be used
for the third reference signal.
Parameter 3-15 Reference 1 Source,
parameter 3-16 Reference 2 Source, and
parameter 3-17 Reference 3 Source
define up to 3 different reference
signals. The sum of these reference
signals defines the actual reference.
Danfoss A/S © 06/2017 All rights reserved.
3-18 Relative Scaling Reference Resource
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select a variable value to be added to the
fixed value (defined in
parameter 3-14 Preset Relative Reference).
The sum of the fixed and variable values
(labeled Y in Illustration 4.9) is multiplied
by the actual reference (labeled X in
Illustration 4.9). This product is then
added to the actual reference (X+X*Y/100)
to give the resulting actual reference.
Y
X
Illustration 4.9 Resulting Actual
Reference
[0]
No function
*
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input
29
[8]
Frequency input
33
[11] Local bus
reference
4.4.3 3-4* Ramp 1
Configure the ramp parameter, ramping times, for each of
the 4 ramps (parameter group 3-4* Ramp 1, parameter
group 3-5* Ramp 2, parameter group 3-6* Ramp 3, and
parameter group 3-7* Ramp 4).
Hz
P 4-14
High-limit
Reference
P 1-23
Motor
frequency
P 4-12
Low limit
P 3-*1
Ramp (X)Up
Time (Acc)
t
acc
Illustration 4.10 Example of Ramp 1
Resulting
Relative
Z
actual
Z=X+X*Y/100
reference
P 3-*2
Time
Ramp (X)
Down
Time (Dec)
t
dec
MG06C702