UPS
1. UPS Cleaning:
openings and replace the filters regularly to prevent any object from blocking or covering
these areas.
2. UPS Regular Inspection:
b. Regularly check the UPS every half year and inspect:
1) Whether the UPS, LED indicators, and alarm function are operating normally.
2) Whether the UPS works in bypass mode (normally, the UPS works in normal mode). If
yes, check if any error, overload, internal fault, etc. occurs.
root cause.
Batteries
The DPH series UPS uses the lead-acid batteries or the lithium-ion batteries. The battery life
depends on the environment temperature, the usage, and the charging/ discharging frequency.
High temperature environments and high charging/ discharging frequency will quickly shorten
the battery life. Please follow the suggestions below to ensure a normal battery lifetime.
1. Keep usage temperature between 15°C ~ 25°C (59°F ~ 77°F).
2. When the UPS needs to be stored for an extended period of time, the lead-acid batteries
must be recharged once every three months and the charging time must not be less than 24
hours each time. As for the lithium-ion batteries, please contact your battery supplier for the
charging frequency and charging duration.
Fans
Higher temperatures shorten fan life. When the UPS is running, please check if all of the fans
work normally and make sure if the ventilation air can move freely around and through the UPS.
If not, replace the fans.
NOTE:
Please ask your local dealer or customer service for more maintenance information. Do
not perform maintenance if you are not trained for it.