4.1.1 Display Port

Before shipment, the display port has been connected to the 10" touch panel with the
designated cable in Delta factory.

4.1.2 REPO Dry Contacts

The REPO dry contacts provide you with quick and convenient interfaces to shut down the
UPS safely when an emergency occurs. Connect the REPO dry contacts to a user-supplied
switch and you can remotely shut down the UPS. The REPO dry contacts provide normally
open (NO) and normally closed (NC) these two options for use.
NOTE:
If you want to enable the normally closed (NC) function, please take out the dry
contact card (see Figure 4-5) and remove its Jump CNR3 (see Figure 4-6) before
you turn on the UPS.