Manual Bypass Mode_ Dual Input_ Parallel Units - Delta Modulon DPH Series User Manual

Three phase 200-600 kva
Hide thumbs Also See for Modulon DPH Series:
Table of Contents

Advertisement

3.2.11 Manual Bypass Mode_ Dual Input_ Parallel Units

WARNING:
1. In Manual Bypass mode, make sure that all of the breakers (except each
3. During Manual Bypass mode, each parallel UPS's input power is completely
4. For parallel UPSs, if you want to turn off one of the parallel UPSs for
In Manual Bypass mode (parallel), if one of the parallel UPSs needs maintenance, please
After confirmation, please follow the procedures below to manually switch each of the
parallel UPSs to Manual Bypass mode.
1
Tap each LCD's ON/ OFF Button (
2
Turn ON each UPS's Manual Bypass Switch (Q3).
3
Turn OFF each UPS's Bypass Switch (Q2).
4
Turn OFF each UPS's Input Switch (Q1) and Output Switch (Q4).
5
Turn OFF each external battery cabinet's breaker (Q5).
In Manual Bypass mode, all power inside the parallel UPSs is completely cut off and
maintenance personnel can perform maintenance safely. Power of the connected critical
loads will be supplied by manual bypass. During Manual Bypass mode (parallel), all parallel
power through the parallel UPSs in Manual Bypass mode.
UPS's Manual Bypass Switch (Q3)) are in the OFF position before working on
any of the parallel UPSs' internal circuits. This avoids electric shock.
no high voltage inside all parallel UPSs and maintenance can be performed
safely. However, to avoid electric shock, please do not touch the following parts
on each parallel UPS: AC Input terminal block, Bypass Input terminal block,
UPS Output terminal block, Battery Input terminal block, grounding terminals
(see Figure 5-8 ~ Figure 5-10 for the location of these terminal blocks and
terminals) and any copper bars connected to the Manual Bypass Switch (Q3),
as they may carry high voltage.
maintenance, please make sure the total connected critical loads will not
exceed the remaining parallel units' total capacity.
) and the 'POWER OFF?' screen will pop up to
Figure 3-25 for the path of electrical
3-25
3
Operation Modes
'YES'.