7.6.4
Battery & Charging Setting
Path:
→ Battery & Charging Setting
Item
Battery Type
Battery Rating Voltage
Battery Strings
Battery Low Warning
Battery Cut Off
Voltage
Capacity
Float Charge Voltage
Delta UPS DPH 50-200kVA
Set up the battery type as VRLA/ LiB (Dry Contact)
(Integration)
.
*2
NOTE:
1. *
If you use non-Delta lithium-ion batteries,
1
please set up the battery type as 'LiB (Dry
Contact)'. Please refer to
Contacts
more information about configurations of the
lithium-ion batteries, please contact Delta
customer service.
2. *
If you use the Delta lithium-ion batteries,
2
please set up the battery type as 'LiB
(Integration)'. The item 'LiB (Integration)' will
appear on the LCD only if you use the Delta
lithium-ion batteries with the optional
multifunctional communication card (MFC)
being installed in the SMART slot. Please
contact Delta customer service if you need
more information.
Set up the battery voltage rating.
Set up how many battery strings that are used on site.
Set up the battery low warning voltage.
Set up the battery low voltage. In Battery mode, when
the battery low voltage is reached, the battery power will
be cut off, and the inverter of the UPS will shut down.
The loads will then be transferred to bypass if the bypass
is available; otherwise, the UPS will shut down.
Set up the battery capacity.
Set up the float charge voltage.
Description
4.1.6 Input Dry
7.10.6 Dry Contact Setting
and
/ LiB
*1
. For
122