Sto Function Pick-Up Time; Sto Function Parameters - Eaton PowerXL DA1 Series Installation Manual

Variabe frequency drives
Hide thumbs Also See for PowerXL DA1 Series:
Table of Contents

Advertisement

2.10.5 STO function pick-up time

2.10.6 STO function parameters

The total pick-up time for the STO function is the time that elapses from the
moment a safety-related event occurs on the system's components
(aggregate) to the moment a safe state is reached (in this case: Stop
category 0 as defined in IEC 60204-1):
The pick-up time from the moment the STO inputs (control signal
terminals 12 and 13) become de-energized to the moment when the
outputs in the power section (U, V, W) are in a state in which no torque
is produced in the motor (STO function activated) is less than 1 ms.
The pick-up time from the moment the STO inputs (control signal
terminals 12 and 13) become de-energized to the moment the STO
monitoring status changes is less than 20 ms.
The pick-up time from the moment a fault is detected in the STO circuit
to the moment Sto-F is signaled (fault indicator, digital output) is less
than 20 ms.
The STO function is always activated and enabled in DA1
variable frequency drives – regardless of the operating mode or
of parameter changes made by the user.
During normal operation (supply voltage present), there are various options
for monitoring the STO inputs' (control signal terminals 12 and 13) state.
If the STO inputs are de-energized:
The corresponding operating unit will display InHibit).
Exception: If the DA1 variable frequency drive detects a fault,
the corresponding fault code will be displayed (not: InHibit).
Relay RO1 will be switched off if parameter P2-15 is set to 13
(changeover contact: 14-16 = open, 14-15 = closed),
Relay RO2 will be switched off if parameter P2-18 is set to 13
(N/O: 17-18 = open).
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
2 Engineering
2.10 STO function
73

Advertisement

Table of Contents
loading

Table of Contents