General Installation Diagram - Eaton PowerXL DA1 Series Installation Manual

Variabe frequency drives
Hide thumbs Also See for PowerXL DA1 Series:
Table of Contents

Advertisement

3.5.7 General installation diagram

PE
B
A
B
A
B
A
≧ 100 mm
(≧ 3.94")
Figure 60: EMC installation
a Mains connection: Supply voltage, central earthing connection for control panel and machine
b External radio interference suppression filter: Optional external radio interference suppression
DX-EMC... radio interference suppression filter for longer motor cables or use in a different EMC
environment
c Control connection: Connecting the digital and analog control lines, STO function and communicating
through an RS45 plug-in connection
d Motor connection: EMC connection (PES) between the screened motor cable and the motor's terminal
box, made according to EMC requirements, with metal cable gland or with gland plate in the terminal
box.
e Cable Routing: Power cables (A) and control cables (B) spatially routed separately from each other.
If different potential levels need to cross, they should do so at right angles as far as possible.
f Cable Routing: Do not route power cables and control cables parallel to each other in a single cable
duct. If they need to be routed in parallel, they should be in separate metal cable ducts (in order to
meet EMC-requirements).
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
~
AC
DC-
L1/L
L2/N
L3
1 2 3 4 5 6 7 8 9 10 11 12 13
COM
14 15 16 17 18
DC+
BR
U
V
W
PES
3 Installation
3.5 EMC installation
PES
PES
PE
U V W
U V W
PES
PE
97