Error Messages; Sto Function Checklist - Eaton PowerXL DA1 Series Installation Manual

Variabe frequency drives
Hide thumbs Also See for PowerXL DA1 Series:
Table of Contents

Advertisement

2 Engineering
2.10 STO function

2.10.7 Error messages

2.10.8 STO function checklist

76
The following table lists the error messages relevant to the STO function, as
well as potential causes and fixes.
Table 4: Error messages
1)
2)
Display
Error code
Modbus RTU [hex]
PS-trP
05
Sto-F
29
1) Display = Error code on the 7-digital display assembly or on the optional DX-KEY-LED2 keypad
2) Modbus RTU [hex] = Hexadecimal fault code via Modbus
A drive's STO function should always be checked before initial
commissioning, after maintenance, and at regular maintenance intervals.
This check should include the following tests:
No.
Activity
1
The STO inputs (control signal terminals 12, 13) are de-
energized. With motor standstill and a stop command
on the DA1 variable frequency drives, InHibit is
displayed (locked state).
2
The STO inputs (control signal terminals 12, 13) are de-
energized and the DA1 variable frequency drive
receives a start command (depending on the selected
mode in P1-13, DI Config Select).
InHibit is displayed (locked state). The motor does
not start.
3
The STO inputs (control signal terminals 12, 13) are
supplied with 24 V DC and the DA1 variable frequency
drive receives a start command (depending on the
selected mode in P1-13, DI Config Select). The motor
starts normally and is controlled by the DA1 variable
frequency drive.
4
The motor is running while being controlled by the
DA1 variable frequency drive and an STO input
(control signal terminal 12 or 13) is de-energized.
InHibitis displayed and the motor coasts.
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Name
Power section fault
Internal STO circuit fault
Note
Potential causes and fixes
• Error message from the power
section's output
• Check the connection to the motor
(short-circuit, earth fault).
• Disconnect the cable from terminals
U, V, W.
If the fault message cannot be reset,
please contact your nearest Eaton
representative.
Please contact your nearest Eaton
representative.

Advertisement

Table of Contents
loading

Table of Contents