6 Specifications

6.1 General rating data

Specifications
General
Standards
Certifications and manufacturer's declarations on conformity
Production quality
Climatic proofing
Ambient temperature range
Operation
IP20 (NEMA 0)
IP55 (NEMA 3)
IP66 (NEMA 4X)
Storage
MTTF
d
MTBF
PFH
D
Electrostatic discharge (ESD, EN 61000-4-2:2009
Fast transient burst (EFT/B, EN 61000-4-4: 2004)
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Symbol
Unit
Value
EMC: EN 61800-3:2004+A1-2012
Radio frequency interference: EN 55011: 2010
Safety: EN 61800-5 : 2007
Protection type: EN 60529: 1992
Note:
DA1-35 ... series devices are not covered by the
EU-EMC Directive declaration of conformity.
CE, UL, cUL, c-Tick, UkrSEPRO, Gost-R
Note:
At the time of writing frame size FS8 is not UL or cUL
Certification.
RoHS, ISO 9001
ρ
%
< 95 %, mean relative humidity (RH),
w
non-condensing (EN 50178)
ϑ
°C
-10 - +50 (frost-free and condensation-free)
ϑ
°C
-10 - +40, with derating of 1.5 % pro °C above 40 °C
on rated operational current I
Note:
Operation within a temperature range of 40 to 50 °C
does not conform to UL Certification.
ϑ
°C
-10 - +40, with derating of 2.5 % pro °C above 40 °C
on rated operational current I
Note:
Operation within a temperature range of 40 to 50 °C
does not conform to UL Certification.
ϑ
°C
-40 - +60
Years
4525
Years
50
1.23 - 09 1/h (0.12 % SIL)
U
kV
±4, contact discharge
±8, air discharge
U
kV
±1, at 5 kHz, control signal terminal
±2, at 5 kHz, motor connection terminals,
Single-phase mains connection terminals
±4, at 5 kHz, three-phase mains connection terminals
6 Specifications
6.1 General rating data
e
e
143