5 Error messages
5.1 Introduction
142
Message
Error no.
42
AtF-03
43
AtF-04
44
AtF-05
49
OVt-Ph
50
Sc-FO1
51
Sc-FO2
52
Sc-FO3
53
Sc-F04
60
OF-01
61
OF-02
70
PLC-01
71
PLC-02
72
PLC-03
73
PLC-04
74
PLC-05
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Possible cause and remedy
Motor identification failed:
The measured motor inductance is too low.
• Make sure that the motor is connected properly and working correctly.
Motor identification failed:
The measured motor inductance is too high.
• Make sure that the motor is connected properly and working correctly.
• Check to make sure that the device's rated output matches the motor's
rated output. The difference should not exceed one full output class.
Motor identification failed:
The measured motor parameters do not match.
• Make sure that the motor is connected properly and working correctly.
• Check to make sure that the device's rated output matches the motor's
rated output. The difference should not exceed one full output class.
A phase in the motor cable is not connected or is broken.
No valid Modbus frame was received within the time specified in P5-06.
• Check to make sure that the network master is working correctly.
• Check connecting cables.
• Increase the value of P5-06 to an acceptable value.
No valid CANopen frame was received within the time specified in P5-05.
• Check to make sure that the network master is working correctly.
• Check connecting cables.
• Increase the value of P5-05 to an acceptable value.
Communications between the device and the plugged-in field bus option have
dropped out.
• Check to make sure that the module is installed properly.
Communications between the device and the plugged-in I/O expansion have
dropped out.
• Check to make sure that the module is installed properly.
No internal connection to an optional card
Optional module in undefined operating state
Non-supported function block from function block editor
Program from function block editor is too big
Division by zero
Lower limit is higher than upper limit
Overflow table Function block editor

Advertisement