Eaton PowerXL DA1 Series Installation Manual page 110

Variabe frequency drives
Hide thumbs Also See for PowerXL DA1 Series:
Table of Contents

Advertisement

3 Installation
3.6 Electrical Installation
3.6.1.5 Stripping lengths and tightening torques
106
PE
A1
Mains
Figure 70: Connection cables
Mains = Electrical supply system (mains voltage),
Motor = Motor connection,
DC-Link = internal DC link,
Brake Resistor = Braking resistor
Table 12: Stripping lengths in the power section
Frame size
A1
(protection)
mm (in)
FS2 (IP20)
8 (0.3)
FS3 (IP20)
8 (0.3)
FS2 (IP66)
10 (0.39)
FS3 (IP66)
10 (0.39)
FS4 (IP20)
15, space unit = ring cable lug, ⌀ M6
FS4 (IP55)
15, space unit = ring-cable lug
FS5 (IP20)
15, space unit = ring-cable lug, ⌀ M8
FS5 (IP55)
15, space unit = ring-cable lug
FS6
Ring-cable lug
FS7
Ring-cable lug
FS8
Ring-cable lug
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
PE
A1
Motor
Tightening torque
Nm (lb-in)
1 (8.85)
1 (8.85)
1.5 (15)
1.5 (15)
2 (18)
4 (35.4)
4 (35.4)
15 (98.2)
20 (177)
20 (177)
57 (504.5)
PE
A1
DC-Link, Brake Resistor

Advertisement

Table of Contents
loading

Table of Contents