DA1-32... series
Size
Rated operational current
Overload current for 60 s every 600 s
Apparent power at rated operation
Rated motor output
Power input side (primary side):
Number of phases
Rated voltage
Input current (phase current)
Minimum braking resistor
Switching frequency (pulse frequency)
Factory default setting
Settings range
Maximum leakage current to earth (PE), without motor
Efficiency
Heat dissipation at I
e
Frame size
Symbol
I
e
I
L
230 V
S
240 V
S
230 V
P
230 V
P
U
LN
I
LN
R
B
f
PWM
f
PWM
I
PE
η
P
V
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Unit
150
180
A
150
180
A
225
270
kVA
59.8
71.7
kVA
62.4
74.8
kW
37
45
HP
50
60
three-phase
V
200 V - 10 % - 240 V +10 %, 50/60 Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
A
172.7
183.3
Ω
6
6
kHz
4
4
kHz
4 - 12
4 - 8
mA
1.54
1.54
0.97
0.98
W
814
945
FS6
FS6
6 Specifications
6.2 Specific rated operational data
202
248
202
248
303
372
80.5
98.8
84
103.1
55
75
75
100
205.7
255.5
6
6
4
4
4 - 16
4 - 12
2.74
2.74
0.98
0.98
1100
1425
FS7
FS7
151