3 Installation

3.3 Assembly

3.3 Assembly
80
The installation guidance provided here takes into account building the
devices into suitable housings with protection rating IP20 and IP55 in
accordance with the EN 60529 standard or other essential provisions that
apply regionally.
The enclosures must be made of a material with high thermal
conductivity.
If a control panel with ventilation openings is used, the openings must
be located above and below the variable frequency drive in order to allow
for proper air circulation. Air should be delivered from the bottom and
conveyed outwards through the top.
If the environment outside the control panel contains dirt particles (e. g.,
dust), a suitable particle filter must be placed on the ventilation openings
and forced ventilation must be used.
The filters must be maintained and cleaned if necessary.
An appropriate enclosed control panel (without ventilation openings)
must be used in environments containing large percentages or amounts
of humidity, salt, or chemicals.
Install the DA1 variable frequency drive only on a nonflammable
mounting base (e.g., on a metal plate).
Figure 42: Surface mounting on metal plate
IP66 DA1 variable frequency drives must be installed as required by the local
conditions for this protection.