1 DA1 device series
1.6 Voltage classes

1.6.4 DA1-35...

32
DA1-35...
Three-phase power supply, rated operating voltage 500/575 V
U
= 3~, 500 - 600 V ±10 %, 50/60 Hz
LN
I
= 2.1 - 34 A
e
Motor: 1.1 - 22 kW (500 V, 50 Hz), 1.5 - 30 HP (575 V, 60 Hz)
FS2, FS3, FS4
L1/L
L1
L2/N
L2
L3
L3
PE
DC+
Figure 20: DA1-35...NB-... (without radio interference suppression filter)
DA1-35...
Three-phase power supply, rated operating voltage 500/575 V
U
= 3~, 500 - 600 V ±10 %, 50/60 Hz
LN
I
= 43 - 150 A
e
Motor: 30 - 110 kW (500 V, 50 Hz), 40 - 150 HP (575 V, 60 Hz)
Mains
FS5, FS6
L1
L1
L2
L2
L3
L3
PE
Figure 21: DA1-34...NB-B55C with DC link choke
(without radio interference suppression filter)
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
I
e
Motor
U
V
M
3 ∼
W
BR
Brake Chopper
I
Motor
e
U
V
W
DC+
BR
Brake Chopper
500 V (U
= 3 ~ 500 V)
LN
575 V (U
= 3 ~ 600 V)
LN
500 V (U
= 3 ~ 500 V)
M
LN
575 V (U
= 3 ~ 600 V)
3 ∼
LN

Advertisement