3 Installation

3.9 Protection against electric shock

3.9 Protection against electric shock
128
Ensuring protection against electric shock when using DA1 variable
frequency drives, as per IEC/EN 61800-5-1
Manufacturer's declaration for the initial verification as per
IEC/HD 60364-6
Fault protection as per IEC/HD 60364-4-41 (DIN VDE 0100-410 (VDE 0100-410))
for the circuit on the output side of the aforementioned equipment is
ensured based on the following requirements:
The installation instructions in this documentation have been observed.
The applicable standards in the IEC/HD 60364 (DIN VDE 0100
(VDE 0100) series have been observed.
The continuity of all associated protective conductors and equipotential
bonding conductors, including the corresponding connection points, has
been ensured.
Provided that the above requirements are met, the aforementioned
apparatus meets the requirements in IEC/HD 60364-4-41 (DIN VDE 0100-410
(VDE 0100-410):2007-06, section 411.3.2.5) when using the "automatic
power supply shutdown" protective measure.
The note is based on the following information:
In the event of a short-circuit with negligible impedance to a protective
conductor or to ground, the aforementioned equipment reduces the output
voltage within the times as per Table 41.1 or otherwise within 5 seconds –
whichever applies – in accordance with IEC/HD 60364-41
(DIN VDE 0100-410; VDE 0100-410):2007-06).
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com