Figure 67. Underload Time Counter Function - Eaton PowerXL DH1 Series Applications Manual

Vfd
Hide thumbs Also See for PowerXL DH1 Series:
Table of Contents

Advertisement

Appendix A—Description of parameters
Code
Modbus ID
Parameter
P6.1.13
319
Underload F0 Torque
This parameter gives value for the minimum torque allowed at zero frequency.
If you change the value of Para ID486, nominal motor current, this parameter is automatically restored to the
default value.
P6.1.14
320
Underload Time Limit
This is the maximum time allowed in an underload condition. An internal up/down counter counts the
accumulated underload time. If the underload counter value goes above this limit, the protection will cause a
trip according to Para ID317. If the drive is stopped, the underload counter is reset to zero.

Figure 67. Underload time counter function

Underload
No Underload
P6.1.15
333
Thermistor Fault Response
This parameter is used to define the device reaction after a "Thermistor Fault Motor" condition occurs. This
failure could be device dependent.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode.
3 = Fault, stop mode after fault always by coasting
P6.1.16
337
PT100 Fault Response
This parameter sets the device reaction after a "PT100 Fault" condition has occurred. This condition could be
possible device dependent.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to standard stop mode
3 = Fault, stop mode after fault always by coasting
P6.1.17
2159
Preheat Mode
This parameter defines the location for enabling or disabling the preheat function where this is used in
the case depending on where the temperature is being read from the drive will turn on the output to allow
current to flow to the motor if the temperature of the drive or PT100 sensor drops, this is typically used when
the motor is not running.
0 = Disable
1 = Enable
174
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Underload
Time Counter
Trip Area
Trip/Warning
P0.15
Time
Application
RO/RW
1,2,3
RW
1,2,3
RW
1,2,3
RW
1,2,3
RW
1,2,3
RW

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents