2 Engineering
2.10 STO function
PNU
Modbus ID
Access right
RUN/ STOP
P2-15
237
RUN
P2-18
240
RUN
74
Table 3: STO-relevant parameters
Name
ro/rw
rw
RO1 function
rw
RO2 function
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Value
Description
0 - 13
Selection of the function of output relay RO1
Possible values:
• 0: RUN, Enable (FWD/REV)
• 1: READY, variable frequency drive ready
for operation
• 2: Speed = speed setpoint value
• 3: Speed > 0
• 4: Speed ≧ Limit: ON: ≧ P2-16;
OFF: < P2-17
• 5: Motor Current ≧ limit: ON: ≧ P2-16;
OFF: < P2-17
• 6: Speed ≧ Limit: ON: ≧ P2-16;
OFF: < P2-17
• 7: Analog input AI2 ≧ Limit: ON: > P2-16;
OFF: < P2-17
• 8: Reserved
• 9: Reserved
• 9: Reserved
• 10: Reserved
• 11: Reserved
• 12: Reserved
• 13: STO (STO = Safe Torque OFF) Status
0 - 13
Selection of the function of output relay RO2
Possible values:
• 0: RUN, Enable (FWD/REV)
• 1: READY, variable frequency drive ready
for operation
• 2: Speed = speed setpoint value
• 3: Speed > 0
• 4: Speed ≧ Limit: ON: ≧ P2-19;
OFF: < P2-20
• 5: Motor Current ≧ limit: ON: ≧ P2-19;
OFF: < P2-20
• 6: Speed ≧ Limit: ON: ≧ P2-19;
OFF: < P2-20
• 7: Analog input AI2 ≧ Limit: ON: > P2-19;
OFF: < P2-20
• 8: Control for the external brake of a hoist.
(Enables the operating mode for hoists).
ON: output frequency ≧ P2-07 with START
(FWD/REV) command present. OFF: Output
frequency ≦ P2-08 with START (FWD/REV)
command not present.
• 9: Reserved
• 9: Reserved
• 10: Reserved
• 11: Reserved
• 12: Reserved
• 13: STO (STO = Safe Torque OFF) Status
DS
1
0