3.6.2.12 IP66, control signal terminals (DA1-...-A6SC)
On DA1 variable frequency drives with IP66 protection and local controls
(DA1-...A6SC), the control signal terminals will be partially wired.
0
REV
FW D
OFF
PW R
ON
Figure 89: DA1-...-A6SC (factory connection)
When supplied, the control signal terminals will be connected as follows:
Table 17: Configuration of the control signal terminals
Terminal
Color
1
RD (red)
2
BU (blue)
3
YE (yellow)
5
GY (gray)
6
WH (white)
7
BK (black)
For the enable signal for operation, you will also need to install
an insulated wire jumper from terminal 1 to terminal 12 (STO+)
and a link from terminal 13 (STO-) to terminal 9 or 7
(→ figure 80, page 112).
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
1 2 3 4 5 6 7 8 9 10
Function
+24 V to FWD/REV selector switch
From selector switch = FWD
From selector switch = REV
+10 V to potentiometer
From potentiometer = f-Set
From potentiometer = 0 V
3 Installation
3.6 Electrical Installation
11
12 13
BK
WH
GY
RD
BU
YE
121