Eaton PowerXL DA1 Series Installation Manual page 148

Variabe frequency drives
Hide thumbs Also See for PowerXL DA1 Series:
Table of Contents

Advertisement

6 Specifications
6.1 General rating data
Specifications
Overvoltage (surge, EN 61000-4-5: 2006)
110 - 115 V, 200 - 240 V
380 - 480 V, 500 - 600 V
Electric strength (flash, EN 61800-5-1: 2007)
110 - 115 V, 200 - 240 V
380 - 480 V, 500 - 600 V
Radio interference class (EMC)
Category and maximum screened motor cable length
with integrated radio interference suppression filter
C1
C2
C3
Installation position
Installation altitude
Protection type
Fan (built-in)
Busbar tag shroud
Main circuit / power section
Power supply
Rated operating voltage
DA1-12...
DA1-32...
DA1-34...
DA1-35...
Mains frequency
Phase imbalance
Maximum short-circuit current (supply voltage)
Mains switch-on frequency
Mains network configuration (AC supply system)
144
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Symbol
Unit
Value
U
kV
±1, phase to phase/neutral conductor
±2, phase/neutral conductor to earth
U
kV
±2, phase to phase
±4, phase to earth
U
kV
1.5
U
kV
2.5
l
m
1
l
m
5
l
m
25
Vertical
h
m
0 - 1,000 above sea level,
> 1,000 with 1 % load current reduction every 100 m,
maximum 2,000 with UL approval,
maximum 4,000 without UL approval
IP20 (NEMA 0)
IP55 (NEMA 3)
IP66 (NEMA 4X)
Yes
BGV A3 (VBG4, finger and back-of-hand proof)
U
V
1~ 230 (200 V -10 % - 240 V +10 %)
e
U
V
3~ 230 (200 V -10 % - 240 V +10 %)
e
U
V
3~ 400 (380 V -10 % - 480 V +10 %)
e
U
V
3~ 575 (500 V - 10 % - 600 V +10 %)
e
f
Hz
50/60 ±10 %
%
max. 3
SCCR
kA
100 (according to IEC 60439-1)
Maximum of once every 30 seconds
TN and TT network with directly earthed neutral point.
IT earthing systems with PCM insulation monitoring
relays only.
Operation on phase-earthed networks is only
permissible up to a maximum phase-earth voltage of
300 V AC.

Advertisement