3 Installation
3.5 EMC installation
92
Route mains and motor cables in the control cabinet as close to
the ground potential as possible. This is because free moving
cables act as antennas.
If routed in parallel, cables carrying high frequencies (e. g.,
screened motor cables) and clean cables (e. g., mains supply
cable, control and signal cables) should be installed at a distance
of at least 100 mm from each other in order to avoid
electromagnetic interference. You should also use separate
cable entries if there is a great difference in voltage potentials.
If control cables and power cables need to cross, they should
always do so at right angles (90°).
≧ 100 mm
(≧ 3.94")
Figure 56: Cable routing
Never lay control or signal cables ② in the same duct as power
cables ①.
Analog signal cables (measured values, setpoints, and
correction values) must be routed inside shielded conduits.
b
b
a
Figure 57: Separate cable routing
a Cable routing: Mains voltage, motor connection
b Control and signal lines, fieldbus connections
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com