3 Installation
3.5 EMC installation
92
→
Route mains and motor cables in the control cabinet as close to
the ground potential as possible. This is because free moving
cables act as antennas.
→
If routed in parallel, cables carrying high frequencies (e. g.,
screened motor cables) and clean cables (e. g., mains supply
cable, control and signal cables) should be installed at a distance
of at least 100 mm from each other in order to avoid
electromagnetic interference. You should also use separate
cable entries if there is a great difference in voltage potentials.
If control cables and power cables need to cross, they should
always do so at right angles (90°).
②
①
≧ 100 mm
(≧ 3.94")
Figure 56: Cable routing
→
Never lay control or signal cables ② in the same duct as power
cables ①.
Analog signal cables (measured values, setpoints, and
correction values) must be routed inside shielded conduits.
b
b
a
Figure 57: Separate cable routing
a Cable routing: Mains voltage, motor connection
b Control and signal lines, fieldbus connections
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com