2.10.2 TÜV certification

2.10.3 Specification of the safety relay

CAUTION
When used in conjunction with permanent magnet motors and
in the unlikely event of multiple output semiconductors (IGBTs)
failing, having the STO function activated may result in a motor
shaft rotational movement of 180 degrees/p = Number of
motor pole pairs).
DANGER
The STO function is an electronic mechanism that does not
provide sufficient protection against electric shock. Additional
potential isolation measures may be accordingly required (e. g.,
switch-disconnector).
DA1 variable frequency drives with a TÜV logo on their nameplate feature an
STO function that complies with the following standards:
Standard
EN 61800-5-2:2007
EN ISO 13849-1:2006
EN 61508 (Part 1 to 7)
EN60204-1
EN 62061
The following information and descriptions for the STO function
are translations of the original description in English (TÜV
specification).
Safety component monitoring requires an approvedsafety relay.
When used together with a DA1 variable frequency drive, the following
minimum requirements must be met for the STO function:
Standard requirement
Number of output contacts
Rated switching voltage
Current carrying capacity
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Classification
Type 2:
"Safely switched-off moment"
PL d
SIL 2
Stop category 0:
"Uncontrolled stopping by means of immediately cutting the
power supply to the machine drive elements"
SIL CL 2
SIL 2 or PL d SC 3 or better with interlocked opposing contacts
Two independent
30 V DC
100 mA (minimum)
2 Engineering
2.10 STO function